LS-6、10型计量箱适用于下列场合的电能计量:
a、农村排灌站,乡镇企业、加工厂、中小型工厂、矿区、交通运输等各种企、事
业单位以及林业、基建工地暂设供电站的高压输电线路的电能计量。
b、小电站发电量计量或小电站电网与国家进行联网运行时互送电能时的计量。
2、使用环境条件:
2.1海拔高度不超过1000m;
2.2环境温度:
高+40℃;
日平均不超过30℃;
低-25℃;
2.3系统接地方式:中性点非有效接地系统;
2.4大气条件:大气中无严重污秽。
使用方法和注意事项:
5.1本产品如用于计量分支线路的电度或用于考核线路损耗时,可将计量
箱安装在电杆的支架上。
5.2用于计量电力变压器高压侧电度时,可与变压器安装在同一个平台上或安装在
电杆上。
5.3新安装运行中的计量箱发现相序相反时,会出现有功电度表仍然正转,无功电
度表反转的现象,造成电度表计量错误,应将计量箱高压侧任意两根对换位置,计量箱
变为正相序进行,才能保证计量箱准确计量。
5.4本产品用于二相一地的电力线路计量电度时,应将地相接在计量箱B相上,其余
二相按正相序连接,防止产生计量的附加误差。
5.5产品吊运时必须使用油箱上的吊攀。
5.6组合互感器的二次接线端子b点和油箱上的接地螺栓应可靠接地,以免造成事故
6、维护和保管:
或补充新油。
6.2计量箱在使用前需要妥善地保管在仓库内,仓库的温度为-25℃至+40℃,相对
湿度不大于85%,通风良好,无腐蚀性气体存在。
7、订货须知:
在订购本型产品时,请详细说明下列项。
7.1产品型号;
7.2额定电压比;
7.3额定电流比;
7.4准确级;
7.5产品使用环境;
7.6单相计量或双向计量
Jls-6 and 10 meter boxes are suitable for the electric energy measurement in the following situations:
A. Rural drainage and irrigation stations, township enterprises, processing plants, small and medium sized factories, mining areas, transportation and other enterprises
Electric energy measurement of high-voltage transmission lines temporarily set up for power supply stations in industrial units and forestry and infrastructure construction sites.
B. Measurement of power generation of small power stations or measurement of power transmission between the power grid of small power stations and the state in connection with the operation of the network.
2. Environmental conditions:
2.1 the altitude shall not exceed 1000m;
2.2 ambient temperature:
High + 40 ℃;
The average no more than 30 ℃;
Low - 25 ℃;
2.3 system grounding: neutral non-effective grounding system;
2.4 atmospheric conditions: there is no serious pollution in the atmosphere.
Usage and precautions:
5.1 this product can be measured if it is used to measure the power of branch lines or when it is used to assess the line loss
The box is mounted on the bracket of the pole.
5.2 when measuring the power transformer's high voltage side power, it can be installed on the same platform or installed on the same platform as the transformer
On the pole.
5.3 when the meter box in the new installation and operation is found to have opposite phase sequence, the active power meter will still turn forward and reactive power will appear
When the meter is reversed, the meter is wrong, and any two of the high-voltage side of the meter box should be replaced
Change into positive phase sequence to ensure accurate measurement of the meter box.
5.4 when the product is used to measure the electrical degree of power lines in two phases and one place, the ground shall be connected to the B phase of the meter box, and the rest
The two phases are connected in a positive phase sequence to prevent additional measurement errors.
5.5 the product must be hoisted by the oil tank.
5.6 the secondary terminal b of the combined transformer and the grounding bolt on the fuel tank shall be reliably grounded to avoid accidents
6. Maintenance and custody:
Or new oil.
6.2 metering box before use to properly keep in the warehouse, the warehouse temperature is 25 ℃ to + 40 ℃, the relative
Humidity not more than 85%, good ventilation, non - corrosive gas presence.
7. Ordering instructions:
Please specify the following items when ordering this model.